Testing
1.TRANSFOEMER RATIO
Specification: S=110VA (ตามข้อมูลการออกแบบ)
Vprimary = 110 V ,Vsecondary = 110 V
ค่ากระแสเต็มพิกัด Ipri(Rated)=1 A , Isec(Rated)=1 A
Insulating Resistance
R Primary=0 Ω R Secondary=0 Ω
R Primary to Core>2000M Ω R Secondary to Core>2000M Ω
R Primary to Secondary>2000M Ω
Transformer Ratio
Vprimary |
00 |
20 |
40 |
60 |
80 |
100 |
120 |
Vsecondary |
00 |
20.02 |
39.98 |
60.06 |
80.30 |
99.90 |
119.3 |
Transformer Ratio |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
Vsecondary |
00 |
20 |
40 |
60 |
80 |
100 |
120 |
Vprimary |
00 |
20.03 |
40.03 |
60.08 |
80.02 |
100.0 |
120.0 |
Transformer Ratio |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
2.APPROXIMATED EQUIVALENT CIRCUIT
Approximated Circuit Test
|
Watt |
Volt |
Amp |
PF |
Note |
Open Circuit Test |
9 |
110.3 |
0.215 |
0.38 |
O/C Secondary Side |
Short Circuit Test |
6.25 |
6.31 |
1.01 |
0.99 |
S/C Secondary Side |
Rp=6.126 Ω Xp=1.226j Ω
Rc=1350.06 Ω Xm=555.219j Ω
3.LOAD TEST
Lamp |
Primary |
|
|
|
Secondary |
|
|
|
W1-W2 |
|
W1 |
V1 |
A1 |
PF1 |
W2 |
V2 |
A2 |
PF2 |
Losses |
0 |
10.2 |
110 |
0.231 |
0.40 |
0 |
110 |
0.026 |
0 |
10.2 |
100W 1 หลอด |
44.03 |
110 |
0.449 |
0.89 |
33.33 |
108.0 |
0.306 |
1 |
10.7 |
100W 2 หลอด |
70.73 |
110 |
0.706 |
0.91 |
64.833 |
106.3 |
0.61 |
1 |
5.897 |
100W 2 หลอด+60W 1 หลอด
|
94.36 |
110 |
0.884 |
0.97 |
82.03 |
105 |
0.78 |
1 |
12.33 |
100W 2 หลอด+60W 1 หลอด+40W 1 หลอด
|
108.8 |
110 |
1.006 |
0.98 |
95 |
104.8 |
0.903 |
1 |
13.8 |
4.POLARITY TEST
V12=110 V , V34=110.4 V, V13=222 V
5.VOLTAGE TAPPING
Designed Voltage |
Measured Value |
Error |
Winding |
Designed Volt/Turns |
Calculated Volt/Turns |
110 |
110.0 |
0 |
348 |
0.31644 |
0.31609 |
24 |
23.94 |
0.06 |
272 |
0.31644 |
0.08801 |
12 |
12.01 |
0.01 |
310 |
0.31644 |
0.03874 |
9 |
8.86 |
0.14 |
320 |
0.31644 |
0.02768 |
3 |
2.830 |
0.17 |
339 |
0.31644 |
0.008348 |
6.STEP-DOWN AUTOTRANSFORMER
Lamp |
Primary |
|
|
|
Secondary |
|
|
|
W1-W2 |
|
W1 |
V1 |
A1 |
PF1 |
W2 |
V2 |
A2 |
PF2 |
Losses |
0 |
0 |
220 |
0 |
0 |
0 |
110.4 |
0.001 |
- |
0 |
1 |
41.75 |
220 |
0.208 |
0.91 |
33.7 |
109.5 |
0.308 |
1 |
8.05 |
2 |
73.75 |
220 |
0.3475 |
0.97 |
64.9 |
108.9 |
0.597 |
1 |
8.85 |
3 |
106.25 |
220 |
0.495 |
0.98 |
96.1 |
108.5 |
0.886 |
1 |
10.15 |
4 |
139.25 |
220 |
0.6425 |
0.99 |
127.2 |
107.9 |
1.179 |
1 |
12.05 |
5 |
171.25 |
219 |
0.79 |
0.99 |
157.6 |
107.4 |
1.467 |
1 |
13.65 |
6 |
202.75 |
219 |
0.93 |
1 |
187.6 |
107 |
1.753 |
1 |
15.15 |
7 |
234.25 |
219 |
1.077 |
0.99 |
217.4 |
106.4 |
2.04 |
1 |
16.85 |
At Full Load Condition: h = 94.27 % Losses = 13.3 W
S1 = 236.5 VA S2 = 216.685 VA
Voltage Regulation = 4.35% แก้ไข
7.STEP-UP AUTOTRANSFORMER
Lamp |
Primary |
|
|
|
Secondary |
|
|
|
W1-W2 |
|
W1 |
V1 |
A1 |
PF1 |
W2 |
V2 |
A2 |
PF2 |
Losses |
0 |
8.475 |
110 |
0.193 |
0.4 |
0 |
218.2 |
0.001 |
- |
8.475 |
1 |
104.25 |
109 |
0.973 |
0.98 |
94.7 |
214.6 |
0.442 |
1 |
9.55 |
2 |
191.25 |
109 |
1.778 |
0.99 |
179 |
179 |
0.851 |
1 |
12.25 |
3 |
225.5 |
108 |
2.097 |
1.00 |
211.6 |
208.8 |
1.014 |
1 |
13.9 |
At Full Load Condition: h = 89.09 % Losses = 12.1 W
S1 = 187 VA S2 = 168.32 VA
Voltage Regulation = 0% แก้ไข
8.VOLTAGE REGULATOR FOR FLUORESCENT LAMP 3x36 W
Select Tap 208V For Load Voltage
Lamp |
Primary |
|
|
|
Secondary |
|
|
|
W1-W2 |
|
W1 |
V1 |
A1 |
PF1 |
W2 |
V2 |
A2 |
PF2 |
Losses |
0 |
0 |
220 |
0 |
0 |
0 |
207.3 |
0 |
- |
0 |
1 |
45.75 |
220 |
0.453 |
0.46 |
35.7 |
208 |
0.397 |
0.44 |
10.05 |
2 |
79.25 |
220 |
0.808 |
0.46 |
67.1 |
207.6 |
0.765 |
0.42 |
12.15 |
3 |
111 |
220 |
0.85 |
0.44 |
98.9 |
207.3 |
0.812 |
0.59 |
12.1 |
At Full Load Condition: h = 89.09 % Losses = 12.1 W
S1 = 187 VA S2 = 168.32 VA
Voltage Regulation = 0%
Select Tap 217V For Load Voltage
Lamp |
Primary |
|
|
|
Secondary |
|
|
|
W1-W2 |
|
W1 |
V1 |
A1 |
PF1 |
W2 |
V2 |
A2 |
PF2 |
Losses |
0 |
0 |
230 |
0 |
0 |
0 |
217.2 |
0 |
- |
0 |
1 |
53.5 |
230 |
0.48 |
0.48 |
38.4 |
214.7 |
0.412 |
0.43 |
15.1 |
2 |
87.25 |
230 |
0.895 |
0.44 |
73.7 |
216.2 |
0.813 |
0.42 |
13.55 |
3 |
120 |
230 |
0.903 |
0.58 |
107.5 |
216 |
0.863 |
0.58 |
12.5 |
At Full Load Condition: h = 89.58 % Losses = 12.5 W
S1 = 207.69 VA S2 = 186.404 VA
Voltage Regulation = 0.55%
คลิ๊กส์ตามหัวข้อที่ต้องการได้ค่ะ
ความหมายของหม้อแปลง : www.108digitalbusiness.com/Build-your-own-transformer.html
หลักการออกแบบหม้อแปลง : www.108digitalbusiness.com/design.html
ขั้นตอนการทำหม้อแปลง : www.108digitalbusiness.com/process.html
การทดสอบหม้อแปลง : www.108digitalbusiness.com/testing.html
รูปประกอบ : www.108digitalbusiness.com/Picture.html